Connecting a PLC
With eDESIGN you can perform an OPC-UA network scan. The web editor has an integrated OPC-UA client with which you can parse the OPC-UA tags from the server and select them accordingly.
Settings in Wago WBM
eDESIGN - PFC with e!Cockpit
-
Check your PFC firmware, it should be >= FW18. Otherwise please update your controller.
-
Download the example project. It is recommended to open the archive, so that the libraries can be installed.
-
To get access to the data points, they must be enabled in the symbol configuration:
If the symbol configuration is missing, it can be added with a right click on Application. -
Here you can decide what will be published.
- Click on the field to activate it
- If you select something that was not previously selected, you must click here
- You must select the same field again, by default it will not be published
- Confirm your selection
-
The same applies if you set checkmarks deeper in the structure tree
- Check the box if you want it to be published
- Make sure you select it again in this section
-
Press the Generate Code key or F11 to compile your settings